Ball-impact resistance of ceilings — what the classes mean

Classes 1A, 2A and 3A from the EN 13964 standard correspond to three ball speeds: 16.5, 8 and 4 m/s. In most halls, class 2A is entirely sufficient for the ceiling, because the ceiling takes hits very differently from the wall behind the goal. We explain where this difference comes from and when 1A is still the right choice.

For designers and contractors working on sports halls, gyms and school corridors — and for clients comparing quotations.

Three classes, three ball speeds

Impact-resistance classes per EN 13964:2014, Annex D
ClassBall speedIn km/hTypical application
1A16,5 ± 0,8 m/s≈ 59Wall panels in the playing-area zone, especially behind the goals. On the ceiling: when it hangs low and the ball can hit it directly at full force, or when the specification requires DIN 18032-3.
2A8,0 ± 0,5 m/s≈ 29Ceiling of most sports halls and gyms — including for indoor football, handball, basketball and volleyball.
3A4,0 ± 0,5 m/s≈ 14Places with a risk of accidental hits: corridors in schools and kindergartens.

Przewiń w poziomie, aby zobaczyć wszystkie kolumny

The ceiling is not a wall: where the ball actually hits

Do the math yourself: at what speed the ball reaches the ceiling

What holds the panel in place

Najczęściej zadawane pytania

  • Which class should be specified for a school gym?
  • Does indoor football need a class 1A ceiling?
  • Does DIN 18032-3 apply in Poland?
  • Does impact resistance mean worse acoustics?